APPENDIX G GRAYWATER SYSTEMS
Title 24, Part 5, California Administrative Code
G-1 Graywater Systems. (General)
(a) The provisions of this Appendix shall apply to the
construction, installation, alteration and repair of graywater systems for
subsurface landscape irrigation. The graywater system shall not be
connected to any potable water system without an air gap (a space or other
physical device which prevents backflow) and shall not result in any
surfacing of the graywater. Except as otherwise provided for in this
Appendix, the provisions of the Uniform Plumbing Code (UPC) shall be
applicable to graywater installations.
(b) The type of system shall be determined on the basis of
location, soil type, and ground water level and shall be designed to
accept all graywater connected to the system from the building. The system
shall discharge into subsurface irrigation fields and may include surge
tank(s) and appurtenances, as required by the Administrative
Authority.
(c) No graywater system, or part thereof, shall be located on
any lot other than the lot which is the site of the building or structure
which discharges the graywater; nor shall any graywater system or part
thereof be located at any point having less than the minimum distances
indicated in Table G-1.
(d) No permit for any graywater system shall be issued until a
plot plan with appropriate data satisfactory to the Administrative
Authority has been submitted and approved. When there is insufficient lot
area or inappropriate soil conditions for adequate absorption of the
graywater, as determined by the Administrative Authority, no graywater
system shall be permitted. The Administrative Authority is a city or
county.
(e) No permit shall be issued for a graywater system which would
adversely impact a geologically sensitive area, as determined by the
Administrative Authority.
(f) Private sewage disposal systems existing or to be
constructed on the premises shall comply with Appendix I of this code or
applicable local ordinance. When abandoning underground tanks, Section
722.0 of the UPC shall apply. Also, appropriate clearances from graywater
systems shall be maintained as provided in Table G-1. The capacity of the
private sewage disposal system, including required future areas, shall not
be decreased by the existence or proposed installation of a graywater
system servicing the premises.
(g) Installers of graywater systems shall provide an operation
and maintenance manual, acceptable to the Administrative Authority, to the
owner of each system. Graywater systems require regular or periodic
maintenance.
(h) The Administrative Authority shall provide the applicant a
copy of this Appendix.

G-2 Definitions.
Graywater is untreated waste water which has not come into contact with
toilet waste. Graywater includes waste water from bathtubs, showers,
bathroom wash basins, clothes washing machines, and laundry tubs, or an
equivalent discharge as approved by the Administrative Authority. It does
not include waste water from kitchen sinks, photo lab sinks, dishwashers,
or laundry water from soiled diapers.
Surfacing of graywater means the ponding, running off, or other release
of graywater from the land surface.

G-3 Permit.
It shall be unlawful for any person to construct, install or alter, or
cause to be constructed, installed or altered any graywater system in a
building or on premises without first obtaining a permit to do such work
from the Administrative Authority.

G-4 Drawings and Specifications.
The Administrative Authority may require any or all of the following
information to be included with or in the plot plan before a permit is
issued for a graywater system:
(a) Plot plan drawn to scale completely dimensioned, showing lot
lines and structures, direction and approximate slope of surface, location
of all present or proposed retaining walls, drainage channels, water
supply lines, wells, paved areas and structures on the plot, number of
bedrooms and plumbing fixtures in each structure, location of private
sewage disposal system and 100 percent expansion area or building sewer
connecting to public sewer, and location of the proposed graywater
system.
(b) Details of construction necessary to ensure compliance with
the requirements of this Appendix together with full description of the
complete installation including installation methods, construction and
materials as required by the Administrative Authority.
(c) A log of soil formations and ground water level as
determined by test holes dug in close proximity to any proposed irrigation
area, together with a statement of water absorption characteristics of the
soil at the proposed site as determined by approved percolation tests. In
lieu of percolation tests, the Administrative Authority may allow the use
of Table G-2, an infiltration rate designated by the Administrative
Authority, or an infiltration rate determined by a test approved by the
Administrative Authority.
(d) A characterization of the graywater for commercial,
industrial, or institutional systems, based on existing records or
testing.

G-5 Inspection and Testing.
(a) Inspection
- 1. All applicable provisions of this Appendix and of Section 103.5
of the UPC shall be complied with.
-
- 2. System components shall be properly identified as to
manufacturer.
-
- 3. Surge tanks shall be installed on dry, level, well-compacted soil
if in a drywell, or on a level, three inch concrete slab or equivalent,
if above ground.
-
- 4. Surge tanks shall be anchored against overturning
-
- 5. If the irrigation design is predicated on soil tests, the
irrigation field shall be installed at the same location and depth as
the tested area.
-
- 6. Installation shall conform with the equipment and installation
methods identified in the approved plans.
-
- 7. Graywater stub-out plumbing may be allowed for future connection
prior to the installation of irrigation lines and landscaping. Stub-out
shall be permanently marked "GRAYWATER STUB-OUT, DANGER UNSAFE WATER."
(b) Testing
- 1. Surge tanks shall be filled with water to the overflow line prior
to and during inspection. All seams and joints shall be left exposed and
the tank shall remain watertight.
-
- 2. A flow test shall be performed through the system to the point of
graywater irrigation. All lines and components shall be watertight.

G-6 Procedure for Estimating Graywater Discharge.
(a) Single Family Dwellings and Multi-Family Dwellings
The Administrative Authority may utilize the graywater discharge
procedure listed below, water use records, or calculations of local daily
per person interior water use:
- 1. The number of occupants of each dwelling unit shall be calculated
as follows:
-
| |
First Bedroom |
2 occupants |
| |
Each additional bedroom |
1 occupant |
-
- 2. The estimated graywater flows of each occupant shall be
calculated as follows:
-
| |
Showers, bathtubs and wash basins |
25 GPD/occupant |
| |
Laundry |
15 GPD/occupant |
-
- 3. The total number of occupants shall be multiplied be the
applicable estimated graywater discharge as provided above and the type
of fixtures connected to the graywater system.
(b) Commercial, Industrial, and Institutional Projects
The Administrative Authority may utilize the graywater discharge
procedure listed below, water use records, or other documentation to
estimate graywater discharge:
- 1. The square footage of the building divided by the occupant load
factor from UPC Table 10-A equals the numbers of occupants.
-
- 2. The number of occupants times the flow rate per person (minus
toilet water and other disallowed sources) from UPC Table I-2 equals the
estimated graywater discharge per day.
The graywater system shall be designed to distribute the total amount
of estimated graywater discharged daily.

G-7 Required Area of Subsurface Irrigation.
Each irrigation zone shall have a minimum effective irrigation area for
the type of soil and infiltration rate to distribute all graywater
produced daily , pursuant to Section G-6, without surfacing. The
required irrigation area shall be based on the estimated graywater
discharge, pursuant to Section G-6, size of surge tank, or a method
determined by the Administrative Authority.
If a mini-leachfield irrigation system is used, the required square
footage shall be determined from Table G-2, or equivalent, for the type of
soil found in the excavation. The area of the irrigation field shall be
equal to the aggregate length of the perforated pipe sections within the
irrigation zone times the width of the proposed mini-leachfield
trench.
No irrigation point shall be within five vertical feet of the highest
known seasonal groundwater nor where graywater may contaminate the
groundwater or ocean water. The applicant shall supply evidence of ground
water depth to the satisfaction of the Administrative Authority.

G-8 Determination of Irrigation Capacity.
(a) In order to determine the absorption quantities of soils
other than those listed in Table G-2, the proposed site may be subjected
to percolation tests acceptable to the Administrative Authority or
determined by the Administrative Authority.
(b) When a percolation test is required, no mini-leach field
system or subsurface drip irrigation system shall be permitted if the test
shows the absorption capacity of the soil is less than 60 minutes/inch or
more rapid than 5 minutes/inch, unless otherwise permitted by the
Administrative Authority.
(c) The irrigation field size may be computed from Table G-2, or
determined by the Administrative Authority or a designee of the
Administrative Authority.

G-9 Surge Tank Construction. (FIG. 1)
(a) Plans for surge tanks shall be submitted to the
Administrative Authority for approval. The plans shall show the data
required by the Administrative Authority and may include dimensions,
structural calculations, and bracing details.
(b) Surge tanks shall be constructed of solid, durable
materials, not subject to excessive corrosion or decay and shall be
watertight.
(c) Surge tanks shall be vented as required by Chapter 9 of this
Code and shall have a locking, gasketed access opening, or approved
equivalent, to allow for inspection and cleaning.
(d) Surge tanks shall have the rated capacity permanently marked
on the unit. In addition, "GRAYWATER IRRIGATION SYSTEM, DANGER - UNSAFE
WATER" shall be permanently marked on the surge tank.
(e) Surge tanks installed above ground shall have an overflow,
separate from the line connecting the tank with the irrigation fields. The
overflow shall have a permanent connection to a sewer or to a septic tank,
and shall be protected against sewer line backflow by a backwater valve.
The overflow shall not be equipped with a shut-off valve.
(f) The overflow and drain pipes shall not be less in diameter
than the inlet pipe. The vent size shall be based on the total graywater
fixture units, as outlined in UPC Table 7-5 or local equivalent. Unions or
equally effective fittings shall be provided for all piping connected to
the surge tank.
(g) Surge tanks shall be structurally designed to withstand
anticipated loads. Surge tank covers shall be capable of supporting an
earth load of not less than 300 pounds per square foot when the tank is
designed for underground installation.
(h) Surge tanks may be installed below ground in a dry well on
compacted soil, or buried if the tank design is approved by the
Administrative Authority. The system shall be designed so that the tank
overflow will gravity drain to a sanitary sewer line or septic tank. The
tank must be protected against sewer line backflow by a backwater
valve.
(i) Materials
-
- 1. Surge tanks shall meet nationally recognized standards for non
potable water and shall be approved by the Administrative Authority.
-
- 2. Steel surge tanks shall be protected from corrosion, both
externally and internally, by an approved coating or by other acceptable
means.

G-10 Valves and Piping. (FIG. 1)
Graywater piping discharging into a surge tank or having a direct
connection to a sanitary drain or sewer piping shall be downstream of an
approved waterseal type trap(s). If no such trap(s) exists, an approved
vented running trap shall be installed upstream of the connection to
protect the building from any possible waste or sewer gasses. Vents and
venting shall meet the requirements in Chapter 9 of the UPC. All graywater
piping shall be marked or shall have a continuous tape marked with the
words "DANGER - UNSAFE WATER." All valves, including the three-way valve,
shall be readily accessible and shall be approved by the Administrative
Authority. A backwater valve, installed pursuant to this Appendix, shall
be provided on all surge tank drain connections to the sanitary drain or
sewer piping.

G-11 Irrigation Field Construction.
The Administrative Authority may permit subsurface drip irrigation,
mini-leach field or other equivalent irrigation methods which discharge
graywater in a manner which ensures that the graywater does not surface.
Design Standards for subsurface drip irrigation systems and mini-leach
field irrigation systems follow:
(a) Standards for a subsurface drip irrigation system are:
- 1. Minimum 140 mesh (115 micron) filter with a capacity of 25
gallons per minute, or equivalent, filtration, sized appropriately to
maintain the filtration rate, shall be used. The filter back-wash and
flush discharge shall be caught, contained and disposed of to the sewer
system, septic tank, or with approval of the Administrative Authority, a
separate mini-leach field sized to accept all the back wash and flush
discharge water. Filter backwash water and flush water shall not be used
for any purpose. Sanitary procedures shall be followed when handling
filter back-wash and flush discharge of graywater.
-
- 2. Emitters shall have minimum flow path of 1200 microns and shall
have a coefficient of manufacturing variation (Cv) of no more than seven
percent. Irrigation system design shall be such that emitter flow
variation shall not exceed plus or minus ten percent. Emitters shall be
recommended by the manufacture for subsurface use and graywater use, and
shall have demonstrated resistance to root intrusion. For emitter
ratings refer to: Irrigation Equipment Performance Report, Drip Emitters
and Micro-Sprinklers, Center for Irrigation Technology, California State
University, 5730 N. Chestnut Avenue. Fresno, California 93740-0018.
-
- 3. Each irrigation zone shall be designed to include no less than
the number of emitters specified in Table G-3, or through a procedure
designated by the Administrative Authority. Minimum spacing between
emitters is 14 inches in any direction.
-
- 4. The system design shall provide user controls, such as valves,
switches, timers, and other controllers as appropriate, to rotate the
distribution of graywater between irrigation zones.
-
- 5. All drip irrigation supply lines shall be polyethylene tubing or
PVC class 200 pipe or better and schedule 40 fittings. All joints shall
be properly solvent-cemented, inspected and pressure tested at 40 psi,
and shown to be drip tight for five minutes, before burial. All supply
lines will be buried at least eight inches deep. Drip feeder lines can
be poly or flexible PVC tubing and shall be covered to a minimum depth
of nine inches.
-
- 6. Where pressure at the discharge side of the pump exceeds 20
pounds per square inch (psi), a pressure reducing valve able to maintain
downstream pressure no greater than 20 psi shall be installed downstream
from the pump and before any emission device.
-
- 7. Each irrigation zone shall include a flush valve/anti-siphon
valve to prevent back siphonage of water and soil.
(b) Standards for a mini-leach field system are:
- 1. Perforated sections shall be a minimum 3-inch diameter and shall
be constructed of perforated high density polyethylene pipe, perforated
ABS pipe, perforated PVC pipe, or other approved materials, provided
that sufficient openings are available for distribution of the graywater
in the trench area. Material, construction and perforation of the piping
shall be in compliance with the appropriate absorption field drainage
piping standards and shall be approved by the Administrative Authority.
-
- 2. Clean stone, gravel, or similar filter material acceptable to the
Administrative Authority, and varying in size between 3/4 inch to 2
inches shall be placed in the trench to the depth and grade required by
this Section. Perforated sections shall be laid on the filter material
in an approved manner. The perforated sections shall then be covered
with filter material to the minimum depth required by this Section. The
filter material shall then be covered with landscape filter fabric or
similar porous material to prevent closure of voids with earth backfill.
No earth backfill shall be placed over the filter material cover until
after inspections and acceptance.
-
- 3. Irrigation fields shall be constructed as follows:
-
| |
Minimum |
Maximum |
| Number of drain lines per irrigation zone |
1 |
--- |
| Length of each perforated line |
--- |
100 feet |
| Bottom width of trench |
6 inches |
18 inches |
| Total depth of trench |
17 inches |
18 inches |
| Spacing of lines, center to center |
4 feet |
--- |
| Depth of earth cover of lines |
9 inches |
--- |
| Depth of filter material cover of lines |
2 inches |
--- |
| Depth of filter material beneath lines |
3 inches |
--- |
| Grade of perforated lines |
level |
3 inches/100 feet |

G-12 Special Provisions.
(a) Other collection and distribution systems may be approved by
the Administrative Authority as allowed by Section 301 of the UPC.
(b) Nothing contained in this Appendix shall be construed to
prevent the Administrative Authority from requiring compliance with
stricter requirements than those contained herein, where such stricter
requirements are essential in maintaining safe and sanitary conditions or
from prohibiting graywater systems. The prohibition of graywater systems
or more restrictive standards may be adopted by the Administrative
Authoriy by ordinance after a public hearing.

G-13 Health and Safety.
(a) Graywater may contain fecal matter as a result of bathing
and/or washing of diapers and undergarments. Water containing fecal
matter, if swallowed, can cause illness in a susceptible person.
Therefore, graywater shall be not be contacted by humans, except as
required to maintain the graywater treatment and distribution system.
(b) Graywater shall not include laundry water from soiled
diapers.
(c) Graywater shall not be applied above the land surface or
allowed to surface and shall not be discharge directly into or reach any
storm sewer system or any water of the United States.
(d) Graywater shall not be used for vegetable gardens.

Table G-1 Location of Graywater System.
| Minimum Horizontal
Distance (in feet) From |
Surge Tank |
Irrigation Field |
- Buildings or Structures (1)
|
5ft (2) |
8ft (3) |
- Property line adjoining private property
|
5ft |
5ft (4) |
- Water supply wells (5)
|
50ft |
100ft |
- Streams and lakes (5)
|
50ft |
50ft |
- Seepage pits or cesspools
|
5ft |
5ft |
- Disposal field & 100% expansion area
|
5ft |
4ft (6) |
- Septic tank
|
0ft |
5ft (7) |
- On-site domestic water service line
|
5ft |
5ft (8) |
- Pressure public water main
|
10ft |
10ft (9) |
- Water ditches
|
50ft |
50ft |
Notes: When mini-leach fields are installed in
sloping ground, the minimum horizontal distance between any part of the
distribution system and ground surface shall be fifteen feet.
(1) Including porches and steps, whether covered or
uncovered, but does not include car ports, covered walks, driveways and
similar structures. (2) The distance may be reduced to zero feet for
above ground tanks if approved by the Administrative Authority. (3) The
distance may be reduced to two feet. (4) For subsurface drip irrigation
systems, 2 feet from property line. (5) Where special hazards are
involved, the distance may be increased by the Administrative
Authority. (6) Applies to the mini-leach fields type system only. Plus
two feet for additional foot of depth in excess of one foot below the
bottom of the drain line. (7) Applies to mini-leach field only. (8)
A two foot separation is required for subsurface drip systems. (9) For
parallel construction or for crossings, approval by the Administrative
Authority shall be required.

Table G-2 Mini-Leach Field Design Criteria of Six Typical
Soils.
| Type of
Soil |
Minimum Sq. Ft. of
Irrigation Area per 100 Gal. of Estimated Graywater Discharge per
Day |
Maximum Absorption
Capacity, Minutes per Inch of Irrigation Area for a 24-Hour
Period |
| Coarse sand or gravel |
20 |
5 |
| Fine sand |
25 |
12 |
| Sandy loam |
40 |
18 |
| Sandy clay |
60 |
24 |
| Clay with considerable sand or gravel |
90 |
48 |
| Clay with small amount of sand or gravel |
120 |
60 |

Table G-3 Subsurface Drip Design Criteria of Six Typical
Soils.
| Type of
Soil |
Maximum Emitter
Discharge (gal/day) |
Minimum Number of
Emitters per gpd of Graywater Production |
| Sand |
1.8 |
0.6 |
| Sandy loam |
1.4 |
0.7 |
| Loam |
1.2 |
0.9 |
| Clay loam |
0.9 |
1.1 |
| Silty clay |
0.6 |
1.6 |
| Clay |
0.5 |
2.0 | Use the daily graywater flow calculated
in Section G-6 to determine the number of emitters per
line. |